The machine manufacturer decides whether or not a password is required.
The probabilities of failure (PFH) and certification of the safety functions also apply without
password.
What do I do if I lose the password?
You have forgotten the password, however, you would nevertheless like to change the
setting of the safety functions.
Procedure
1. Create a new project for the converter using Startdrive.
Leave all the factory setting in the project.
2. Load the project in the converter.
After loading, the converter has the factory settings.
3. Recommission the converter.
You can obtain more information or learn about alternative procedures from Technical
Support.
Parameters
Parameter
p9761
p9762
p9763
7.15.2.3

Configuring a safety function

Overview
To ensure protection against unauthorized changes, it is recommended that you configure the
safety function settings.
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Description
SI password input
SI password new
SI password acknowledgment
Advanced commissioning
7.15 Safe Torque Off (STO) safety function
Setting
Enters the Safety Integrated password.
0: No password set (factory setting)
1 ... FFFF FFFF: Password is set
Enters a new Safety Integrated password.
Acknowledges the new Safety Integrated pass‐
word.
237