9.6 List of alarms and faults
Number
Cause
F01018
Power-up aborted more than once
A01028
Configuration error
F01033
Unit switchover: Reference parame‐
ter value invalid
F01034
Unit switchover: Calculation of the
parameter values after reference
value change unsuccessful
F01040
Parameters must be saved
F01044
Loading of memory data card defec‐
tive
A01101
Memory card not available
F01105
CU: Insufficient memory
F01122
Frequency at the probe input too
high
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01512
An attempt has been made to estab‐
lish an conversion factor for scaling
which is not present
A01590
Motor maintenance interval lapsed
F01662
CU hardware fault
A01910
Setpoint timeout
F01910
F03505
Analog input, wire break
A03560
Local/Remote keyswitch in the "Off"
position
A03561
A03561(0): Local drive control
 
A03561(1): Remote drive control
(e.g. via Startdrive) failed because
the Local/Remote keyswitch is set to
"Local"
382
Remedy
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the converter.
Explanation: Parameterization on the memory card has been created with a
different type of module (article number, MLFB)
Check the module parameters and recommission if necessary.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters involved
can be calculated in the per unit notation (p0304, p0305, p0310, p0596,
p2000, p2001, p2002, p2003, r2004).
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
Insert a memory card or disable the warning A01101.
Activating message for a memory card that is not inserted (Page 357)
Reduce number of data records.
Reduce the frequency of the pulses at the probe input.
Contact technical support.
Replace CU.
Create scaling or check transfer value.
Carry out maintenance and reset the maintenance interval (p0651).
Switch CU off and on again, upgrade firmware, or contact technical support.
The alarm is generated when p2040 ≠ 0 ms and one of the following causes
is present:
The bus connection is interrupted
Communications error (CRC, parity bit, logical error)
An excessively low value for the fieldbus monitoring time (p2040)
Check the connection to the signal source for interrupts.
Check the level of the signal supplied.
The input current measured by the analog input can be read out in r0752.
Set the keyswitch to another position (e.g. "Local" or "Remote").
Note: Active faults are acknowledged if the keyswitch is turned from the
"Off" position to "Local" or "Remote".
The Local/Remote keyswitch is set to "Local" and the drive is controlled lo‐
cally. If required, set the keyswitch to "Remote" and control it remotely.
Set the keyswitch to "Remote" position for remote control
Deactivate remote control for local control
Note: Active faults are acknowledged if the keyswitch is turned from the
"Off" position to "Local" or "Remote".
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA