Changing the assignment of the digital inputs
Parameter
p3330[0 ... n] =
722.x
p3331[0 ... n] =
722.x
p3332[0 ... n] =
722.x
7.4.5

Three-wire control, method 2

The "Enable" command is a precondition for switching on the motor. The "ON" command
switches the motor on. The "Reversing" command inverts the motor direction of rotation.
Removing the enable switches the motor off (OFF1).
Enable/OFF1
Parameters
Select three-wire control, method 2
Parameter
p0015 = 64
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
7.4 Controlling clockwise and counter-clockwise rotation via digital inputs
Description
BI: 2/3 wire control command 1 (enable/OFF1)
BI: 2/3 wire control command 2 (ON clockwise rotation)
BI: 2/3 wire control command 3 (ON counter-clockwise rotation)
Example: p3332 = 722.0 ⇒ DI 0: ON counter-clockwise rotation
ON
0
0 or 1
1
0→1
1
0→1
Description
Macro drive unit
You must carry out quick commissioning in order to set parameter p0015.
Assigning digital inputs DI to the commands:
DI 0: Enable/OFF1
DI 1: ON
DI 2: Reversing
Reversing
Function
0 or 1
OFF1: The motor stops.
0
ON: Clockwise motor rotation.
1
ON: Counter-clockwise motor rotation.
Advanced commissioning
141