Siemens SINAMICS G115D Operating Instructions Manual page 122

Distributed drive for conveyor applications
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Commissioning
6.4 Quick commissioning
The geared motor of the G115D Motor Mounted drive has been parameterized before factory
delivery.
• Configure your motor in either of the following ways:
– Enter the motor data according to the rating plate of your motor.
– If you use a Siemens motor, select a motor based on its article number. In this case, the
• Set the motor connection (star/delta) and the 87 Hz characteristic.
• Select the temperature sensor for monitoring of the motor temperature.
• Select to reverse the output phase sequence or not.
Define whether the converter actuates a motor holding brake.
Set the most important parameters to suit your application.
• Select the technological application:
– [0]: In all applications that do not fall under [3]
– [3]: Applications involving pumps and fans with optimized efficiency. The setting only
• Set the motor data identification:
– [1]: Recommended setting for "speed control" control type. Measure the motor data at
– [2]: Measure the motor data at standstill. The converter switches off the motor after the
– [3]: Measure the motor data while the motor is rotating. The converter switches off the
• Calculate the motor parameters.
Enter the encoder data if you use an HTL encoder for the positioning function via PLC.
Set the check mark as follows to save your data in the converter and the memory card (if
inserted) so that it is not lost if the power fails. Click on the
You have entered all of the data that is necessary for the quick commissioning of the
converter.
120
values of the selected motor are taken as default motor data.
makes sense for steady-state operation with slow speed changes.
standstill and with the motor rotating. The converter switches off the motor after the
motor data identification has been completed.
motor data identification has been completed.
Recommended setting for the following cases:
⇒ You have selected "Speed control" as control mode, however the motor cannot freely
rotate, e.g. for mechanically limited traversing sections.
⇒ You have set "U/f control" as control mode.
motor after the motor data identification has been completed.
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
button.