Alarms, faults and system messages
9.5 Faults, fault buffer and fault history
Parameters
Parameters of the fault buffer and the fault history
Parameter
r0945[0 ... 63]
r0948[0 ... 63]
r0949[0 ... 63]
p0952
r2109[0 ... 63]
r2130[0 ... 63]
r2131
r2133[0 ... 63]
r2136[0 ... 63]
Extended settings for faults
Parameter
You can change up to 20 different faults into alarms, suppress faults, modify the fault response, or modify
the acknowledgment mode:
p2100[0 ... 19]
p2101[0 ... 19]
p2118[0 ... 19]
380
Description
Fault code
Fault time received in millisec‐
onds
Fault value
Fault cases counter
Fault time removed in milli‐
seconds
Fault time received in days
Actual fault code
Fault value for float values
Fault time removed in days
Description
Changing fault response,
fault number
Changing the fault reaction,
reaction
Changing message type, mes‐
sage number
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Setting
Displays the numbers of the faults that have occur‐
red.
Displays the system runtime in milliseconds when
the fault occurred.
Displays additional information about the fault that
occurred (as integer number).
Number of fault cases that have occurred since the
last acknowledgment.
With p0952 = 0, you delete the fault buffer and the
fault history.
Factory setting: 0
Displays the system runtime in milliseconds when
the fault was removed.
Displays the system runtime in days when the fault
occurred.
Displays the code of the oldest active fault.
Displays additional information about the fault that
occurred for float values.
Displays the system runtime in days when the fault
was removed.
Setting
Selects the faults for which the fault response
should be changed.
Factory setting: 0
Sets the fault reaction for the selected fault.
0: NONE
1: OFF1
2: OFF2
3: OFF3
5: STOP2
6: Internal armature short-circuit / DC braking
Factory setting: 0
Selects faults or alarms for which the message type
should be changed.
Factory setting: 0
SINAMICS G115D Wall Mounted distributed drive