Advanced commissioning
7.7 Drive control via AS-i
Macro 31: AS-i Dual Slave with fixed setpoint
The control accesses the two slaves of the converter each via four bits.
Via Slave 2, in accordance with profile 7.A.E, the control specifies the speed setpoint via the
motor control bits (AS-i.DO0 ... AS-i.DO2).
Via Slave 1, the control sends data in cyclical or acyclical mode, in accordance with profile
7.A.5.
The control requires one bit per slave in order to specify the slave.
Macro 31, Slave 2 with profile 7.A.E: Control → Converter
• AS-i.DO0
• AS-i.DO1
• AS-i.DO2
• AS-i.DO3
If the control specifies the speed setpoint, the converter replies:
Macro 31, Slave 2 with profile 7.A.E: Converter → control
• p2080[0] = 53.13
• p2080[1] = 899.11
• p2080[2] = 722.0
• p2080[3] = 722.1
If the control sends a diagnostic request via AS-i.P0, the converter replies with the currently
pending fault or alarm messages.
(Page 178)
Macro 31, Slave 1 with profile 7.A.5: Control → Converter
• AS-i.DO0
• AS-i.DO1
• AS-i.DO2
• AS-i.DO3
Macro 31, Slave 1 with profile 7.A.5: Converter → control
• p2080[4] = 722.2
• p2080[5] = 722.3
176
→
p1020.0 = 2093.0
→
p1021.0 = 2093.1
→
p1022.0 = 2093.2
→
Select Slave A or Slave B, interconnected internally
Fixed speeds via the motor control bits and response in the converter (Page 178)
PLC ready to switch on
Pulses enabled
State DI0
State DI1
Alarm and fault messages via RP0 ... RP3 from the converter to the AS-i master
→
Time signal for the CTT2 (Combined Transaction Type 2) transfer from
the AS-i master
→
Data bit for the CTT2 transfer, four bytes cyclically or acyclically via PIV
(parameter channel). The reading and writing of parameters is possible
via the PIV. Because data is transferred bit-by-bit, the read and write
process is very slow.
→
p3390 = 2093.4
→
Select Slave A or Slave B, interconnected internally
State DI2
State DI3
Fixed speed bit 0
Fixed speed bit 1
Fixed speed bit 2
→
AS-i.DI0
→
AS-i.DI1
→
AS-i.DI2
→
AS-i.DI3
Override quick stop
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
→
AS-i.DI0
→
AS-i.DI1