Summary of Contents for Siemens SINAMICS G120P

  • Page 3 ___________________ Safety information ___________________ General ___________________ SINAMICS Mechanical installation ___________________ Electrical installation SINAMICS G120P Line filter ___________________ Technical specifications Operating Instructions Control version V4.7 05/2017 A5E32844996B AE...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Safety information ........................... 7 Warnings ........................... 7 Components that can be destroyed by electrostatic discharge (ESD) ........9 General ..............................11 Mechanical installation .......................... 15 Electrical installation..........................17 Technical specifications ........................19 Line filter Operating Instructions, 05/2017, A5E32844996B AE...
  • Page 6 Table of contents Line filter Operating Instructions, 05/2017, A5E32844996B AE...
  • Page 7: Safety Information

    Safety information Warnings WARNING Danger to life if the fundamental safety instructions and remaining risks are not carefully observed Non-compliance with the fundamental safety instructions and residual risks stated in Chapter 1 of the Installation Manual for PM330 Power Modules can result in accidents with severe injuries or death.
  • Page 8 Safety information 1.1 Warnings Note Support by SIEMENS service centers We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. Line filter Operating Instructions, 05/2017, A5E32844996B AE...
  • Page 9: Components That Can Be Destroyed By Electrostatic Discharge (Esd)

    Safety information 1.2 Components that can be destroyed by electrostatic discharge (ESD) Components that can be destroyed by electrostatic discharge (ESD) CAUTION Components sensitive to electrostatic charge The board contains components that can be destroyed by electrostatic discharge. These components can be easily destroyed if not handled properly. If you do have to use electronic boards, however, please observe the following: •...
  • Page 10 Safety information 1.2 Components that can be destroyed by electrostatic discharge (ESD) Line filter Operating Instructions, 05/2017, A5E32844996B AE...
  • Page 11: General

    General Description The line filters limit the conducted interference emitted by the converter units to permissible values. To reduce emissions, the Power Modules are equipped as standard with a line filter in accordance with the limit values defined in category C3 (environment 2). The additional line filters described here can be fitted for use in environment 1 (category C2).
  • Page 12 General CAUTION Risk of burns due to high surface temperatures of the line filter The line filter can become very hot. You can get seriously burnt when touching the surface. • Mount the line filter so that contact is not possible. If this is not possible, attach a clearly visible and understandable warning notice at hazardous positions.
  • Page 13 General WARNING Danger to life due to high leakage currents caused by an interrupted external protective conductor The drive components conduct a high leakage current via the protective conductor. Touching conductive parts when the protective conductor is interrupted can result in death or serious injury.
  • Page 14 General NOTICE Damage to the line filter through overheating when operated on the system without active operation of the converter Connection of the line filter to the supply system with no active converter operation can lead to overload and damage to the line filter through overheating. •...
  • Page 15: Mechanical Installation

    Mechanical installation When the line filter is installed in a cabinet, it must be positioned directly beside the Power Module. The line reactor must be positioned between the line filter and Power Module. Cabling must be kept as short as possible. To prevent interference being injected into the interference-suppressed line cable (this can, in some cases, nullify the effects of the line filter), the line cable to the line filter must be routed separately from other cables.
  • Page 16 Mechanical installation Dimension drawing Figure 3-1 Dimension drawing, line filter Table 3- 1 Dimensions of the line filter (all data in mm) 6SL3000-0BE33- 6SL3000-0BE35- 6SL3760-0MR00- 6SL3760-0MS00- 1AA0 0AA0 0AA0 0AA0 49.5 78.2 127.5 127.5 Lengths n1 and n2 correspond to the distance between holes Line filter Operating Instructions, 05/2017, A5E32844996B AE...
  • Page 17: Electrical Installation

    Electrical installation Connection When connecting the line filter and line reactor, you must take into account the following conditions to ensure that they function correctly: ● Use shielded control cables. The shield must be connected at both ends. ● With analog control cables, connecting the shield at both ends can result in coupled-in noise.
  • Page 18 Electrical installation Tightening torques for screw connections The following tightening torques apply when tightening current-conducting connections (DC link connections, motor connections, busbars, cable lugs) and other connections (ground connections, protective ground connections, steel threaded connections/glands). Table 4- 1 Tightening torques for screw connections Thread Ground connections, protective Aluminum threaded connec-...
  • Page 19: Technical Specifications

    Technical specifications General technical data Table 5- 1 General technical data Line frequency 47 ... 63 Hz Product standard EN 61800-5-1 Overload capacity 1.60 x I for 3 s followed by 1.36 x I for 60 s followed by 1.00 x I for 240 s Specific technical data Table 5- 2...
  • Page 20 Technical specifications Table 5- 3 Technical data, line filter 3 AC 500 V – 690 V Article number 6SL3760-0MS00- 0AA0 Rated voltage 3 AC 500 –10 % to 3 AC 690 +10 % (-15 % < 1 min) Rated current I 1200 Power loss 0.112...