Advanced commissioning
7.6 Drive control via Ethernet/IP
5. Switch off the converter power supply.
6. Wait until all LEDs on the converter are dark.
7. Switch on the converter power supply again.
You have now configured the converter for communication via Ethernet/IP.
Parameters
Parameter
p2030
p8920
p8921
p8922
p8923
p8925
r8931
r8932
r8933
p8980
p8981
158
Description
Fieldbus interface protocol selec‐
tion
PN Name of Station
PN IP Address
PN Default Gateway
PN Subnet Mask
Activate PN interface configuration Setting to activate the interface configuration
PN IP Address actual
PN Default Gateway actual
PN Subnet Mask actual
Ethernet/IP profile
Ethernet/IP ODVA STOP mode
Setting
0: No protocol
7: PROFINET
10: Ethernet/IP
The default setting is dependent upon the convert‐
er.
Sets the station name for the onboard PROFINET
interface.
Sets the IP address for the onboard PROFINET inter‐
face.
Factory setting: 0
Sets the default gateway for the onboard PROFINET
interface.
Factory setting: 0
Sets the subnet mask for the onboard PROFINET
interface.
Factory setting: 0
0: No function (factory setting)
2: Activate and save configuration
3: Delete configuration
Displays the actual IP address.
Displays the actual default gateway.
Displays the actual subnet mask.
Sets the profile for Ethernet/IP.
0: SINAMICS
1: ODVA AC/DC
Sets the STOP mode for the Ethernet/IP ODVA pro‐
file (p8980 = 1).
0: OFF1 (factory setting)
1: OFF2
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA