Changing the number of command data sets
1. Set p0010 = 15.
2. The number of command data sets is configured with p0170.
3. Set p0010 = 0.
You have changed the number of command data sets.
Copying command data sets
1. Set p0809[0] to the number of the command data set whose settings you wish to copy
(source).
2. Set p0809[1] to the number of the command data set in which you wish to copy the settings.
3. Set p0809[2] = 1 to start the copying.
4. The converter sets p0809[2] = 0 after the copying finishes.
You have copied the settings of a command data set into another command data set.
Example
As in the example above, you obtain the interconnection if you configured the interfaces of
the converter accordingly.
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
7.10 Switching over the drive control (command data set)