Siemens SINAMICS G115D Operating Instructions Manual page 168

Distributed drive for conveyor applications
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Advanced commissioning
7.6 Drive control via Ethernet/IP
Siemens Drive Object, Instance Number: 32C hex
Supported services
Class
Class Attribute
No.
1
2
3
Instance Attribute
No.
2
3 ... 1
8
19
20 ... 
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
166
• Get Attribute single
Service
Type
get
UINT16
get
UINT16
get
UINT16
Type
Service Name
INT16
get, set
Commissioning state
WORD
get
STW1
WORD
get
Main setpoint
WORD
get
ZSW1
WORD
get
Actual Frequency
REAL
get, set
Ramp Up Time
REAL
get, set
Ramp Down Time
REAL
get, set
Current Limit
REAL
get, set
Frequency MAX Limit
REAL
get, set
Frequency MIN Limit
REAL
get, set
OFF3 Ramp Down Time
UINT32 /
get, set
PID Enable
BOOL
REAL
get, set
PID Filter Time Constant p2265 technology controller actual value filter
REAL
get, set
PID D Gain
REAL
get, set
PID P Gain
REAL
get, set
PID I Gain
REAL
get, set
PID Up Limit
REAL
get, set
PID Down Limit
REAL
get
Speed setpoint
REAL
get
Output Frequency
REAL
get
Output Voltage
REAL
get
DC Link Voltage
Instance
Name
Revision
Max Instance
Num of Instances
Value/explanation
p0010   commissioning parameter filter
STW1 bit-by-bit access:
Attr.3   = STW1.0
Attr.18 = STW1.15
Main setpoint
ZSW1 bit-by-bit access:
Attr.20 = ZSW1.0
Attr.35 = ZSW1.15
Main actual value (actual frequency)
p1120[0]   ramp-function generator ramp-up
time
p1121[0]   ramp-function generator ramp-
down time
p0640[0]   current limit
p1082[0]   maximum speed
p1080[0]   minimum speed
p1135[0]   OFF3 ramp-down time
p2200[0]   technology controller enable
time constant
p2274   technology controller differentiation
time constant
p2280 technology controller proportional gain
p2285   technology controller integral time
p2291   technology controller maximum limit‐
ing
p2292 technology controller minimum limiting
r0020   speed setpoint
r0024   output frequency
r0025   output voltage
r0026[0]   DC link voltage
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA