Mounting
4.1 Mounting the G115D Wall Mounted drive
Restrictions:
For wall-mounted converter FSA and FSB (≤3 kW), the permissible output current is reduced for mounting
orientations
②③④
Mounting clearance
To guarantee full performance under all conditions, the minimum clearance distances are as
follows:
• Wiring side of the converter: 200 mm (7.9 in)
Non-wiring side of the converter: 150 mm (5.9 in)
• Side-by-side: no clearance distance is required between the converters.
40
to
.
Derating the output current to 80% of the rated converter current is necessary.
Derating the output current to 70% of the rated converter current is necessary.
SINAMICS G115D Wall Mounted distributed drive