Wiring
5.9 Connecting the line supply
QUICKON/MQ15 connector* (daisy-chain connections not supported)
X1 - line supply (IN), 4-pin, male
* Not suitable for UL applications; not available for FSC
Glanded variant
X1/X3 - line supply terminals (screw-type)
Motor-mounted converter
Screw tightening torque: 1.75 Nm/
15.5 lbf.in
For wall-mounted converter, you must remove the local/remote control (LRC) panel or the
blanking cover to get access to the line supply terminals.
Further information
70
Cables and connectors (Page 64)
Glanded installation kit (Page 36)
Wall-mounted converter
Screw tightening torque:
1.7 Nm/15.0 lbf.in (for terminals in
green)
1.3 Nm/10.5 lbf.in (for terminals in
black)
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Signal
Description
L1
Line phase L1
L2
Line phase L2
L3
Line phase L3
Protective earth
Signal
Description
L1
Line phase L1
L2
Line phase L2
L3
Line phase L3
PE
Protective earth
Cable gland size: M25 * 1.5