Acceptance test STO (basic functions)

Procedure
To perform an acceptance test of the STO function as part of the basic functions, proceed as
follows:
1.
2.
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
The converter is ready
The converter signals neither faults nor alarms of the safety functions (r0945[0...7],
r2122[0...7]).
STO is not active (r9773.1 = 0).
Switch on motor
2.1.
Enter a speed setpoint ≠ 0.
2.2.
Switch on the motor (ON command).
2.3.
Check that the correct motor is running.
A.2 Acceptance tests for the safety functions
Appendix
Status
 
 
 
 
 
 
 
585