6.6

Restoring the factory settings

When must you restore the factory settings?
Restore the converter to the factory settings in the following cases:
• You do not know the converter settings.
• The line voltage was interrupted during commissioning and you were not able to complete
commissioning.
Restoring the factory settings when the safety functions are enabled
If you are using the integrated safety functions of the converter, e.g. "Safe Torque Off", you must
reset the safety functions separately from the remaining converter settings.
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
 Overview of the manuals (Page 588)
Commissioning
6.6 Restoring the factory settings
125