Encoder Interface X2 - Siemens SIMOVERT SLP Operating Instructions Manual

Simolink pulse generator
Table of Contents

Advertisement

Connections
5.2

Encoder interface X2

5-2
02.2001
The encoder interface of the SIMOLINK Pulse Generator is the 9-pin,
SUB D socket with screw locking mechanism (UNC) on the front of the
housing. Two RS422 drivers each supply two signals per pulse output,
one signal with non-inverted signal level and one signal with inverted
signal level. The driver voltage supply circuit is isolated from the 24 V
supply for the module.
Frequency
generator
Fig. 5-2
Schematic of output circuit (connector X2)
The two operating modes "90° pulses" and "100 kHz signal" are
selected via a jumper in the encoder connector. The 90° pulses setting
is the default and is activated when pin 1 in the encoder interface is
unused.
Pin
Signal
2
A+
7
A–
4
B+
9
B–
1
SEL_100 kHz
3, 8
GND
5, 6
n.c.
Housing
Outer shield
9-pin SUB D socket with screw locking mechanism (UNC)
Table 5-2
Assignment of connector X2 for 90° pulses mode
P5
Meaning for 90° pulses
Track A not inverted
Track A inverted
Track B not inverted
Track B inverted
Do not assign,
selection of 100-kHz signal
Ground (see below)
Unused
GWE-477 764 4070.76 J
Operating Instructions
SIMOLINK Pulse Generator
2
A+
7
A−
4
B+
9
B−
1
SEL_100 kHz
3,8
GND
Range
RS422
standard
RS422
standard
Do not
insert
jumper to
GND!