Advanced commissioning
7.4 Controlling clockwise and counter-clockwise rotation via digital inputs
Changing the assignment of the digital inputs
Parameter
p0840[0...n] =
722.x
p1113[0...n] =
722.x
7.4.2

Two-wire control, method 2

Commands "ON/OFF1 clockwise rotation" and "ON/OFF1 counter-clockwise rotation" switch
on the motor - and simultaneously select a direction of rotation. The converter only accepts a
new command when the motor is at a standstill.
ON/OFF1 clockwise rota‐
Parameters
Select two-wire control, method 2
Parameter
p0015 = 61
138
Description
BI: ON/OFF1 (ON/OFF1)
Example: p0840 = 722.3 ⇒ DI 3: ON/OFF1
BI: Setpoint inversion (reversing)
ON/OFF1 counter-clock‐
tion
wise rotation
0
1
0
1
Description
Macro drive unit
You must carry out quick commissioning in order to set parameter p0015.
Assigning digital inputs DI to the commands:
DI 0: ON/OFF1 clockwise rotation
DI 1: ON/OFF1 counter-clockwise rotation
Function
0
OFF1: The motor stops.
0
ON: Clockwise motor rotation.
1
ON: Counter-clockwise motor rotation.
1
ON: The motor direction of rotation is defined
by the command that first reaches state "1".
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA