Siemens G130 List Manual page 1730

Hide thumbs Also See for G130:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
Bit 17: Fault in the multiturn.
Bit 23: Temperature outside the limit values.
Note:
For an encoder version that is not described here, please contact the encoder manufacturer for more detailed
information on the bit coding.
Remedy:
- determine the detailed cause of the fault using the fault value.
- if required, replace the DRIVE-CLiQ encoder.
F31142 (N, A)
Encoder 1: Battery voltage fault
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Encoder 1
Reaction:
ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
When switched-off, the encoder uses a battery to back up the multiturn information. The battery voltage is no longer
sufficient to check the multiturn information.
Remedy:
Replace battery.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31150 (N, A)
Encoder 1: Initialization error
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Sensor Module Encoder 1
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2)
Infeed: NONE
Acknowledge:
PULSE INHIBIT
Cause:
Encoder functionality selected in p0404 is not operating correctly.
Fault value (r0949, interpret hexadecimal):
Encoder malfunction.
The bit assignment corresponds to that of p0404 (e.g. bit 5 set: Error track C/D).
See also: p0404 (Encoder configuration effective), p0491 (Motor encoder fault response ENCODER)
Remedy:
- check that p0404 is correctly set.
- check the encoder type used (incremental/absolute) and for SMCxx, the encoder cable.
- if relevant, note additional fault messages that describe the fault in detail.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31151 (N, A)
Encoder 1: Encoder speed for initialization AB too high
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Sensor Module Encoder 1
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2)
Infeed: NONE
Acknowledge:
PULSE INHIBIT
Cause:
The encoder speed is too high while initializing the Sensor Module.
Remedy:
Reduce the speed of the encoder accordingly during initialization.
If necessary, deactivate monitoring (p0437.29).
See also: p0437 (Sensor Module configuration extended)