Siemens G130 List Manual page 1580

Hide thumbs Also See for G130:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
A07558 (F)
Encoder 2: Reference point coordinate not in the permissible range
Message value:
%1
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The reference point coordinate received when adjusting the encoder via connector input CI:p2599 lies outside the
half of the encoder range and cannot be set as actual axis position. The maximum permissible value is displayed in
the supplementary information.
Remedy:
Set the reference point coordinate less than the value from the supplementary information.
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A07559 (F)
Encoder 3: Reference point coordinate not in the permissible range
Message value:
%1
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The reference point coordinate received when adjusting the encoder via connector input CI:p2599 lies outside the
half of the encoder range and cannot be set as actual axis position. The maximum permissible value is displayed in
the supplementary information.
Remedy:
Set the reference point coordinate less than the value from the supplementary information.
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
F07560
Drive encoder: Number of pulses is not to the power of two
Message value:
Encoder data set: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Reaction:
Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For rotary absolute encoders, the pulse number in p0408 must be to the power of two.
Fault value (r0949, interpret decimal):
The fault value includes the encoder data set number involved.
Remedy:
- check the parameterization (p0408, p0404.1, r0458.5).
- upgrade the Sensor Module firmware if necessary
F07561
Drive encoder: Number of multiturn pulses is not to the power of two
Message value:
Encoder data set: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Reaction:
Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The multiturn resolution in p0421 must be to the power of two.
Fault value (r0949, interpret decimal):
The fault value includes the encoder data set number involved.
Remedy:
- check the parameterization (p0421, p0404.1, r0458.5).
- upgrade the Sensor Module firmware if necessary
1580