Siemens G130 List Manual page 1597

Hide thumbs Also See for G130:
Table of Contents

Advertisement

F07810
Drive: Power unit EEPROM without rated data
Message value:
-
Message class:
Hardware/software error (1)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
No rated data are stored in the power unit EEPROM.
See also: p0205 (Power unit application), r0206 (Rated power unit power), r0207 (Rated power unit current), r0208
(Rated power unit line supply voltage), r0209 (Power unit maximum current)
Remedy:
Replace the power unit or inform Siemens Customer Service.
F07815
Drive: Power unit has been changed
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The code number of the actual power unit does not match the saved number. This only occurs if the comparator in
p9906 or p9908 is not at 2 (low) or 3 (minimum).
Fault value (r0949, interpret decimal):
Number of the incorrect parameter.
See also: r0200 (Power unit code number actual), p0201 (Power unit code number)
Remedy:
- Connect the original power unit and switch on the Control Unit again (POWER ON).
- set p0201 to r0200 and exit commissioning with p0010 = 0.
Note:
If the power unit type was changed (see r0203) or the motor replaced, then the motor must be recommissioned (e.g.
using p0010 = 1, p3900 = 3, p1900 = 1, 2). This is also necessary if motor data is still to be downloaded via DRIVE-
CLiQ.
If the new power unit is accepted, then if required, the current limit p0640 can be reduced by a lower maximum
current of the power unit (r0209) (torque limits stay the same).
If the comparison stage in p9906 is set to 2, 3, then commissioning can be exited (p0010 = 0) and the fault
acknowledged. This procedure is not recommended for different power unit types.
See also: r0200 (Power unit code number actual)
F07815
Drive: Power unit has been changed
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF
Component:
Power Module
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The code number of the actual power unit does not match the saved number. This only occurs if the comparator in
p9906 or p9908 is not at 2 (low) or 3 (minimum).
Fault value (r0949, interpret decimal):
Number of the incorrect parameter.
See also: r0200 (Power unit code number actual), p0201 (Power unit code number)
Remedy:
Connect the original power unit and switch on the Control Unit again (POWER ON) or set p0201 to r0200 and exit
commissioning with p0010 = 0.
For infeeds, the following applies:
Line reactors or line filters must be used that are specified for the new power unit. A line supply and DC link
identification routine (p3410 = 5) must then be carried out. It is not possible to change the power unit without re-
commissioning the system if the type of infeed (A_Infeed, B_Infeed, S_Infeed), the type of construction/design
(booksize, chassis) or the voltage class differ between the old and new power units.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1597

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents