F06909
Braking Module internal Vce fault
Message value:
%1
Message class:
Braking Module faulted (14)
Drive object:
B_INF
Component:
None
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
In the power unit, the monitoring of the collector-emitter voltage (U_ce) of the power semiconductor to control the
braking resistor has responded.
Possible causes:
- short circuit at the braking resistor terminals.
- defective power semiconductor in the braking resistor control.
Note:
Under certain circumstances, this alarm is also output if a braking resistor has not been connected and power is fed
back into the Braking Module.
See also: r3689 (Digital Braking Module Uce fault)
Remedy:
- connect a braking resistor.
- check the braking resistor connection.
- check the braking resistor.
- carry out a POWER ON (switch-off/switch-on).
- replace the unit.
A06921 (N)
Braking resistor phase unsymmetry
Message value:
-
Message class:
Braking Module faulted (14)
Drive object:
VECTOR_G
Component:
Motor
Reaction:
NONE
Acknowledge:
NONE
Cause:
- the three resistors of the braking chopper are not symmetrical.
- DC link voltage oscillations caused by fluctuating loads of the connected drives.
Remedy:
- check the feeder cables to the braking resistors.
- if required, increase the value for detecting asymmetry (p1364).
See also: p1360 (Braking chopper braking resistor cold), p1362 (Braking chopper activation threshold), r1363
(Braking chopper output voltage), p1364 (Braking chopper resistor asymmetry)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F06922
Braking resistor phase failure
Message value:
%1
Message class:
Braking Module faulted (14)
Drive object:
VECTOR_G
Component:
Motor
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A phase failure for the brake resistor was detected.
Fault value (r0949, interpret decimal):
11: Phase U
12: Phase V
13: Phase W
See also: p3235 (Phase failure signal motor monitoring time)
Remedy:
Check the feeder cables to the braking resistors.
See also: p1360 (Braking chopper braking resistor cold), p1362 (Braking chopper activation threshold), r1363
(Braking chopper output voltage), p1364 (Braking chopper resistor asymmetry)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1533

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents