F30682
SI Motion P2: Monitoring function not supported
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The monitoring function enabled in p9301, p9501, p9601, p9801, p9306, p9506, p9307 or p9507 is not supported in
this firmware version.
Note:
This message does not result in a safety stop response.
Fault value (r0949, interpret decimal):
1: Monitoring function SLP not supported (p9301.1).
2: Monitoring function SCA not supported (p9301.7 and p9301.8 ... 15).
3: Monitoring function SLS override not supported (p9301.5).
4: Monitoring function external ESR activation not supported (p9301.4).
5: Monitoring function F-DI in PROFIsafe not supported (p9301.30).
6: Enable actual value synchronization not supported (p9301.3).
9: Monitoring function not supported by the firmware or enable bit not used.
12: This Control Unit does not support operation of safety functions with a higher-level control (e.g. SINUMERIK).
24: Monitoring function SDI not supported.
26: Hysteresis and filtering for SSM monitoring function without an encoder not supported (p9301.16).
27: This hardware does not support onboard F-DI and F-DO.
30: The firmware version of the Motor Module is older than the version of the Control Unit.
33: Safety functions without selection not supported (p9601.5, p9801.5).
34: This module does not support safe position via PROFIsafe.
36: Function "SS1E" not supported.
39: This module or software version of the CU/MM does not support safe gearbox stage switchover (p9501.26).
44: this module/this software version does not support referencing via the safety control channel (p9501.27).
50: Shortening the switchover times for SOS (p9569/p9369, p9567/p9367) is not supported.
52: "SBR with encoder" function is not supported (p9306 = 2).
53: function SS2E not supported (p9301.18).
Remedy:
- deselect monitoring function involved (p9301, p9501, p9601, p9801, p9307, p9507, p9506, p9306).
- Upgrade the Motor Module firmware.
Note:
ESR: Extended Stop and Retract
F-DI: Failsafe Digital Input
SBR: Safe Brake Ramp (safe brake ramp monitoring)
SCA: Safe Cam / SN: Safe software cam
SDI: Safe Direction (safe motion direction)
SI: Safety Integrated
SLP: Safely Limited Position / SE: Safe software limit switches
SLS: Safely Limited Speed / SG: Safely reduced speed
SP: Safe Position
SS1E: Safe Stop 1 External (Safe Stop 1 with external stop)
SS2E: Safe Stop 2 external (Safe Stop 2 with external stop, external STOP D)
See also: p9301 (SI Motion enable safety functions (Motor Module)), p9501 (SI Motion enable safety functions
(Control Unit)), p9503 (SI Motion SCA (SN) enable (Control Unit)), p9601 (SI enable functions integrated in the drive
(Control Unit)), p9801 (SI enable functions integrated in the drive (Motor Module)), r9871 (SI common functions
(Motor Module))