Siemens G130 List Manual page 1588

Hide thumbs Also See for G130:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
A07589
Encoder 3: Position actual value preprocessing does not have a valid encoder
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Encoder 3
Reaction:
NONE
Acknowledge:
NONE
Cause:
The following problem has occurred during the position actual value preprocessing.
- an encoder data set has been assigned, however, the encoder data set does not contain any encoder data (p0400
= 0) or invalid data (e.g. p0408 = 0).
Remedy:
Check the drive data sets, encoder data sets.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0189
(Encoder 3 encoder data set number), p0400 (Encoder type selection)
A07590 (F)
Encoder 1: Drive Data Set changeover in operation
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Drive Data Set changeover (DDS) with a change of the mechanical relationships and the encoder assignment
(p2502) was requested in operation.
Remedy:
To changeover the drive data set, initially, exit the "operation" mode.
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A07591 (F)
Encoder 2: Drive Data Set changeover in operation
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Drive Data Set changeover (DDS) with a change of the mechanical relationships and the encoder assignment
(p2502) was requested in operation.
Remedy:
To changeover the drive data set, initially, exit the "operation" mode.
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A07592 (F)
Encoder 3: Drive Data Set changeover in operation
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Drive Data Set changeover (DDS) with a change of the mechanical relationships and the encoder assignment
(p2502) was requested in operation.
Remedy:
To changeover the drive data set, initially, exit the "operation" mode.
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
1588
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150