Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the line phase connection.
- check the motor feeder cable connections.
If there is no phase failure of the line or motor, then line asymmetry is involved.
- reduce the power in order to avoid fault F30011.
F30059
Power unit: Internal fan faulty
Message value:
-
Message class:
Auxiliary unit faulted (20)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The internal power unit fan has failed and is possibly defective.
Remedy:
Check the internal fan and replace if necessary.
F30060 (A)
Precharge contactor state monitoring
Message value:
Fault cause: %1 bin
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A feedback signal for the precharging contactor (ALM, SLM, BLM diode) or the line contactor (BLM thyristor)
interconnected and the monitoring activated.
After switching-in/switching-out the contactor, a correct feedback signal was not received within the monitoring time
set in p0255[0, 2].
Fault value (r0949, interpret binary):
Bit 0: The time set in p0255[0, 2] was exceeded when switching-in/switching-out the contactor.
Bit 1: The precharging contactor was opened while precharging or in the infeed mode (BLM thyristor).
Bit 2: The precharging contactor was switched-in in the OFF state or during infeed operation.
Remedy:
- check the monitoring time setting (p0255[0, 2]).
- check the contactor wiring and activation.
- replace the contactor.
See also: p0255 (Power unit contactor monitoring time)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F30061 (A)
Bridging contactor monitoring
Message value:
Fault cause: %1 bin
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A feedback signal for the bypass contactor is interconnected and the monitoring activated.
After switching-in/switching-out the contactor, a correct feedback signal was not received within the monitoring time
set in p0255[1, 3].
Fault value (r0949, interpret binary):
Bit 0: The time set in p0255[1, 3] was exceeded when switching-in/switching-out the contactor.
Bit 1: The bypass contactor was opened in operation.
Bit 2: The bypass contactor was switched-in in the OFF state or during precharging.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1669