Siemens G130 List Manual page 1747

Hide thumbs Also See for G130:
Table of Contents

Advertisement

F31804 (N, A)
Encoder 1: Checksum error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Sensor Module Encoder 1
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE)
Infeed: OFF2 (NONE)
Acknowledge:
POWER ON (IMMEDIATELY)
Cause:
A checksum error has occurred when reading-out the program memory on the Sensor Module.
Fault value (r0949, interpret hexadecimal):
yyyyxxxx hex
yyyy: Memory area involved.
xxxx: Difference between the checksum at POWER ON and the actual checksum.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
- carry out a POWER ON (switch off/on).
- upgrade firmware to later version (>= V2.6 HF3, >= V4.3 SP2, >= V4.4).
- check whether the permissible ambient temperature for the component is maintained.
- replace the Sensor Module.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31805 (N, A)
Encoder 1: EEPROM checksum error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Sensor Module Encoder 1
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE)
Infeed: OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
Replace the module.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31806 (N, A)
Encoder 1: Initialization error
Message value:
%1
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Sensor Module Encoder 1
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE)
Infeed: OFF2 (NONE)
Acknowledge:
PULSE INHIBIT
Cause:
The encoder was not successfully initialized.
Fault value (r0949, interpret hexadecimal):
Bit 0, 1: Encoder initialization with the motor rotating has failed (deviation involving coarse and fine position in
encoder pulses/4).
Bit 2: Mid-voltage matching for track A unsuccessful.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1747

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents