4 Faults and alarms
4.2 List of faults and alarms
Bit 7: Hardware fault at the EnDat connection of the converter.
Note:
If the encoder cables 6FX2002-2EQ00-.... and 6FX2002-2CH00-.... are interchanged, this can result in the encoder
being destroyed because the pins of the operating voltage are reversed.
Remedy:
For fault value, bit 0 = 1:
- correct encoder cable connected?
- check the plug connections of the encoder cable.
- SMC30: Check the parameterization (p0404.22).
For fault value, bit 1 = 1:
- correct encoder cable connected?
- replace the encoder or encoder cable.
For fault value, bit 2 = 1:
- correct encoder cable connected?
- replace the encoder or encoder cable.
For fault value, bit 3 = 1:
- correct encoder cable connected?
- replace the encoder or encoder cable.
For fault value, bit 5 = 1:
- Measuring unit correctly connected at the converter?
- Replace the measuring unit or the cable to the measuring unit.
For fault value, bit 6, 7 = 1:
- Replace the defective EnDat 2.2 converter.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F32121 (N, A)
Encoder 2: Coarse position error
Message value:
-
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
VECTOR_G
Component:
Encoder 2
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
PULSE INHIBIT
Cause:
For the actual value sensing, an error was detected on the module.
As a result of this error, it must be assumed that the actual value sensing supplies an incorrect coarse position.
Remedy:
Replace the motor with DRIVE-CLiQ or the appropriate Sensor Module.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F32122
Encoder 2: Internal power supply voltage faulty
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Component:
Sensor Module Encoder 2
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
Fault in internal reference voltage of ASICs for encoder 2.
Fault value (r0949, interpret decimal):
1: Reference voltage error.
2: Internal undervoltage.
3: Internal overvoltage.
Remedy:
Replace the motor with DRIVE-CLiQ or the appropriate Sensor Module.
1770
Propagation:
LOCAL
Propagation:
GLOBAL