Hide thumbs Also See for G130:
Table of Contents

Advertisement

2: Brake was accidentally assigned to the spindle (p1215 = 1); this is not permitted for this software release.
3: An attempt was made to enable the function "Safe brake control" (SBC, p9602 = p9802 = 1) for the spindle. This is
not permitted for this software release.
Remedy:
Check whether the motor holding brake has been assigned to one S120 Combi feed drive exclusively (p1215 = 1 or
2).
The fault will only be withdrawn once the motor holding brake has been assigned to just one of the S120 Combi feed
drives (p1215 = 1 or 2 for this one drive). From this point, the motor holding brake will be controlled by this drive.
See also: p1215 (Motor holding brake configuration)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F07935 (N)
Drive: Incorrect motor holding brake configuration
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
An incorrect motor holding brake configuration was detected.
Fault value (r0949, interpret decimal):
0:
A motor holding brake was detected where the brake control has not been configured (p1215 = 0).
The brake control configuration was set to "motor holding brake the same as sequence control" (p1215 = 1) (only
when commissioning for the first time).
For a chassis unit with Safe Brake Adapter (SBA), the interconnection p9621 = r9872.3 was established (only when
commissioning for the first time).
For a parallel connection, the power unit was set in p7015, to which the motor holding brake is connected (only when
commissioning for the first time).
1:
A motor holding brake was detected where the brake control has not been configured (p1215 = 0).
The brake control configuration was left at "No motor holding brake available" (p1215 = 0).
11:
The identification had detected more than one motor holding brake for a parallel connection.
12:
For the parallel connection, in p0121 there is no valid component number for the power unit data set that is set in
p7015.
13:
With the "Safe brake control" (SBC) function activated, an attempt was made to change the value in p7015.
14:
For a parallel connection, the power units set in p7015 cannot be addressed.
Remedy:
For fault value = 0:
- no remedy required.
For fault value = 1:
- if required change the motor holding brake configuration (p1215 = 1, 2).
- if this fault value unexpectedly occurs, then the motor connections should be checked in order to rule out that they
have been interchanged.
For fault value = 11:
For a parallel connection, only connect one motor holding brake.
For fault value = 12:
Check the setting of the power unit data set for a parallel connection (p7015).
For fault value = 13:
Before changing p7015, deactivate the "Safe brake control" function (SBC) (p9602).
For fault value = 14:
Check whether the power unit supports the brake control for a parallel connection (r9771.14).
Check whether there is a DRIVE-CLiQ communication error between the Control Unit and the power unit involved
and, if required, carry out a diagnostics routine for the faults identified.
See also: p1215 (Motor holding brake configuration)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1615