4 Faults and alarms
4.2 List of faults and alarms
For fault value = 2:
- check parameters p9500 and p9300 to see if they are the same (if Safety message C30711 is displayed at the
same time).
For fault value = 400000 hex:
- ensure that the Control Unit is connected to the Power Module.
A30666 (F)
SI Motion P2: Steady-state (static) 1 signal at the F-DI for safe acknowledgment
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
NONE
Cause:
A logical 1 signal is present at the F-DI configured in p10106 for more than 10 seconds.
If, at the F-DI no acknowledgment was performed for safe acknowledgment, then a steady-state logical and 0 signal
must be present. This avoids unintentional safety-relevant acknowledgment (or the "Internal Event Acknowledge"
signal) if a wire breaks or one of the two digital inputs bounces.
Remedy:
Set the fail-safe digital input (F-DI) to a logical 0 signal (p10106).
Note:
F-DI: Failsafe Digital Input
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY
F30672
SI P2: Control Unit software incompatible
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The existing Control Unit software does not support the safe drive-based motion monitoring function.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check whether there are faults in the safety function alignment between the two monitoring channels (F01655,
F30655) and if required, carry out diagnostics for the faults involved.
- use a Control Unit that supports the safe motion monitoring function.
- upgrade the Control Unit software.
Note:
SI: Safety Integrated
F30674
SI Motion P2: Safety function not supported by PROFIsafe telegram
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The monitoring function enabled in p9301 and p9801 is not supported by the currently set PROFIsafe telegram
(p9811).
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret bitwise binary):
Bit 18 = 1:
SS2E via PROFIsafe is not supported (p9301.18).
1686
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150