4 Faults and alarms
4.2 List of faults and alarms
F06906 (A)
Braking Module internal fault
Message value:
%1
Message class:
Braking Module faulted (14)
Drive object:
B_INF
Component:
None
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The internal Braking Module outputs a fault due to overcurrent or an excessively high I2t value and is therefore
inhibited.
Note:
This message is also displayed via BO: p3686.
Fault value (r0949, interpret bitwise binary):
Bit 0 = 1: I2t exceeded
Bit 1 = 1: overcurrent
See also: r3686 (Digital Braking Module fault)
Remedy:
Reduce the number of braking operations.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F06907
Braking Module internal overtemperature
Message value:
-
Message class:
Braking Module faulted (14)
Drive object:
B_INF
Component:
None
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
The temperature sensor connected to the braking resistor signals an overtemperature.
The Braking Module is still active. If the overtemperature persists for more than 60 s, fault F06908 is output, and the
braking module is switched off.
See also: r3687 (Digital Braking Module pre-alarm overtemperature)
Remedy:
- reduce the temperature at the sensor.
- check the temperature sensor connection.
F06908
Braking Module internal overtemperature shutdown
Message value:
-
Message class:
Braking Module faulted (14)
Drive object:
B_INF
Component:
None
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
Braking module shut down due to overtemperature at the temperature sensor of the braking resistor.
The overtemperature is detected by the sensor for longer than 60 s.
See also: r3688 (Braking Module internal overtemperature shutdown)
Remedy:
- reduce the temperature at the sensor.
- check the temperature sensor connection.