Siemens G130 List Manual page 1663

Hide thumbs Also See for G130:
Table of Contents

Advertisement

F30040
Power unit: Undervolt 24 V
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The undervoltage threshold of the 24 V power supply for the power unit was fallen below for longer than 3 ms.
Note:
- for booksize power units, the undervoltage threshold is 15 V.
- for CU310-2, CUA31 and CUA32 the undervoltage threshold is 16 V.
- for all other power units, the undervoltage threshold depends on the power unit, and is not displayed.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
F30040
Power unit: Undervolt 24 V
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
B_INF
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The undervoltage threshold of the 24 V power supply for the power unit was fallen below for longer than 3 ms.
Note:
- for booksize power units, the undervoltage threshold is 15 V.
- for all other power units, the undervoltage threshold depends on the power unit, and is not displayed.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
A30041 (F)
Power unit: Undervoltage 24 V alarm
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the lower threshold has been violated.
Alarm value (r2124, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- check the power supply of the power unit.
- carry out a POWER ON (switch-off/switch-on) for the component.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1663