Siemens G130 List Manual page 1667

Hide thumbs Also See for G130:
Table of Contents

Advertisement

A30049
Power unit: Internal fan faulty
Message value:
-
Message class:
Auxiliary unit faulted (20)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
NONE
Cause:
The internal fan has failed.
Remedy:
Check the internal fan and replace if necessary.
F30050
Power unit: 24 V supply overvoltage
Message value:
-
Message class:
Supply voltage fault (overvoltage) (3)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The voltage monitor signals an overvoltage fault on the module.
Remedy:
- check the 24 V power supply.
- replace the module if necessary.
F30051
Power unit: Motor holding brake short circuit detected
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A short-circuit at the motor holding brake terminals has been detected.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the motor holding brake for a short-circuit.
- check the connection and cable for the motor holding brake.
F30052
EEPROM data error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
EEPROM data error of the power unit module.
Fault value (r0949, interpret decimal):
0, 2, 3, 4:
The EEPROM data read in from the power unit module are incorrect.
1:
EEPROM data is not compatible to the firmware of the power unit application.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
For fault value = 0, 2, 3, 4:
Replace the power unit module or update the EEPROM data.
For fault value = 1:
The following applies for CU31x and CUA31:
Update the firmware \SIEMENS\SINAMICS\CODE\SAC\cu31xi.ufw (cua31.ufw)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
LOCAL
Propagation:
GLOBAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1667