Siemens G130 List Manual page 1633

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Reaction upon A:
NONE
Acknowl. upon A:
NONE
F08500 (A)
COMM BOARD: Monitoring time configuration expired
Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Reaction:
Vector: OFF1 (OFF2, OFF3)
Infeed: OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the configuration has expired.
Fault value (r0949, interpret decimal):
0: The transfer time of the send configuration data has been exceeded.
1: The transfer time of the receive configuration data has been exceeded.
Remedy:
Check communications link.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F08501 (N, A)
PN/COMM BOARD: Setpoint timeout
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
B_INF, ENC, TM120, TM150, TM31, VECTOR_G
Component:
None
Reaction:
Vector: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Infeed: OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The reception of setpoints from the COMM BOARD has been interrupted.
- bus connection interrupted.
- controller switched off.
- controller set into the STOP state.
- COMM BOARD defective.
Remedy:
- Restore the bus connection and set the controller to RUN.
- if the error is repeated, check the update time set in the bus configuration (HW Config).
See also: p8840 (COMM BOARD monitoring time)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F08502 (A)
PN/COMM BOARD: Monitoring time sign-of-life expired
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Reaction:
Vector: OFF1 (OFF2, OFF3)
Infeed: OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the sign-of-life counter has expired.
The connection to the COMM BOARD was interrupted.
Remedy:
- check communications link.
- check COMM BOARD.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1633