Oracle X5-2L Service Manual page 96

Table of Contents

Advertisement

Remove a Power Supply
3.
Gain access to the rear of the server where the faulty power supply is located.
4.
If the cable management arm (CMA) is installed, disconnect both CMA left-side
connectors and move the CMA out of the way.
For instructions for disconnecting the CMA left-side connectors, refer to
Management Arm" in "Oracle Server X5-2L Installation Guide
Caution -
support the CMA so that it does not hang down under its own weight and stress the right-side
connectors; otherwise, the CMA might be damaged. You must continue to support the CMA
until you have reconnected both of the left-side connectors.
5.
Disconnect the power cord from the faulty power supply.
6.
Grasp the power supply handle and push the power supply latch to the left [1].
FIGURE   24
Pull the power supply out of the chassis [2].
7.
Caution -
supply; otherwise, the server might overheat due to improper airflow.
8.
Continue to
96
Oracle Server X5-2L Service Manual • May 2015
When disconnecting the CMA left-side connectors, be sure to use your arm to
Removing a Power Supply
Whenever you remove a power supply, you should replace it with another power
"Install a Power Supply" on page
"Remove the Cable
".
97.