7.2

Saving the settings to a PC

You can transfer the inverter settings to a PG/PC, or vice versa, the data from a PG/PC to the
inverter.
Requirements
● The inverter power supply has been switched on.
● One of the commissioning tools STARTER or Startdrive is
installed on the PG/PC.
● PC and inverter are connected with one another via a USB cable
or the fieldbus
Inverter → PC/PG
Procedure with STARTER
To back up the settings with STARTER, proceed as follows:
1. Go online:
2. Click the "Download project to PG" button:
3. Save the project:
4. Wait until STARTER reports that data backup has been completed.
5. Go offline:
You have backed up the settings with STARTER.
Procedure with Startdrive
To back up the settings with Startdrive, proceed as follows:
1. Go online.
2. Select "Online" > "Upload device to PG/PC."
3. Back up the project with "Project" > "Save."
4. Wait until Startdrive reports that data backup has been completed.
5. Go offline.
You have backed up the settings with Startdrive.
PC/PG → inverter
Procedure
To transfer the settings, proceed as follows:
1. Go online with STARTER :
2. Select the button "Download project to target system":
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Tools to commission the inverter (Page 146)
.
.
.
Saving the settings and series commissioning
.
.
7.2 Saving the settings to a PC
.