Three-Wire Control, Method 1 - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Advanced commissioning
6.2 Inverter control
6.2.7

Three-wire control, method 1

With one control command, you enable the two other control commands. You switch the
motor off by withdrawing the enable (OFF1).
You switch the motor's direction of rotation to clockwise rotation with the positive edge of the
second control command. If the motor is still switched off, switch it on (ON).
You switch the motor's direction of rotation to counter-clockwise rotation with the positive
edge of the third control command. If the motor is still switched off, switch it on (ON).
Image 6-8
Table 6- 10
Enable / OFF1
Parameter
p0015 = 19
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p3330[0 ... n] = 722.x
p3331[0 ... n] = 722.x
p3332[0 ... n] = 722.x
168
Three-wire control, method 1
Function table
ON clockwise
rotation
0
0 or 1
1
0→1
1
0
1
1
Description
Macro drive unit
Controlling the motor using
the digital inputs of the in-
verter:
BI: 2/3 wire control command 1 (enable/OFF1)
BI: 2/3 wire control command 2 (ON clockwise rotation)
BI: 2/3 wire control command 3 (ON counter-clockwise rotation)
Example: p3332[0] = 722.0 ⇒ if CDS 0 (index[0]) is selected, the inverter
receives its ON counter-clockwise command via DI 0.
ON counter-
Function
clockwise rotation
0 or 1
OFF1: The motor stops.
0
ON: Clockwise motor rotation.
0→1
ON: Counter-clockwise motor rota-
tion.
1
OFF1: The motor stops.
DI 0
Enable /
OFF1
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
DI 1
DI 2
ON clockwise
ON counter-
rotation
clockwise
rotation
Converter with CU250S-2 Control Unit

Advertisement

Table of Contents
loading

Table of Contents