Goodrive350 IP55 High-ingress Protection Series VFD
The control performance of the VFD is based on accurate motor models. Therefore, you need
to carry out motor parameter autotuning before running a motor for the first time (taking motor
1 as an example).
Input motor nameplate
Note:
Motor parameters must be set correctly according to the motor nameplate.
If rotary autotuning is selected during motor autotuning, disconnect the motor from the
load to put the motor in static and no-load state. Otherwise, the motor parameter
autotuning results may be incorrect. In addition, autotune P02.06–P02.10 for AMs and
autotune P02.20–P02.23 for SMs.
Synchronous
motor
P02.00=1
(P02.15–P02.19)
Complete parameter
rotary autotuning
Ready
P00.01=0 (controlled by
keypad)
Motor type
(P02.00)
Set autotuning mode
(P00.15)
Complete parameter
static autotuning
Press "RUN" key to start
autotuning
During autotuning
Autotuning finished
-62-
Basic operation guidelines
Asynchronous
motor
P02.00=0
Input motor nameplate
(P02.01–P02.05)
Partial parameter rotary
autotuning