Goodrive350 IP55 High-ingress Protection Series VFD
Function
Name
code
Transmission error
P14.05
processing
Modbus
communication
P14.06
processing action
selection
User-defined
P14.07
running command
address
User-defined
P14.08
frequency setting
address
Modbus TCP
P14.09
communication
timeout period
Enabling 485
P14.10
upgrade program
Description
In general, the function code is set to 0.0. When
continuous communication is required, you can
set the function code to monitor communication
status.
0: Report an alarm and coast to stop
1: Keep running without reporting an alarm
2: Stop according to the stop mode without
generating alarms
(only in the communication-based control
mode)
3: Stop according to the stop mode without
generating alarms
(in all control modes)
0x000–0x111
Ones place:
0: Respond to write operations
1: Not respond to write operations
Tens place:
0: Communication password protection is
invalid.
1: Communication password protection is valid.
Hundreds place: (valid for RS485
communication only)
0: User-defined addresses specified by P14.07
and P14.08 are invalid.
1: User-defined addresses specified by P14.07
and P14.08 are valid.
0x0000–0xFFFF
0x0000–0xFFFF
0.0–60.0s
0–1
0: Disable
-203-
Function parameter list
Default Modify
0
0x000
0x2000
0x2001
5.0s
0