Advertisement

Goodrive350 IP55 High-ingress Protection Series VFD
Function
Name
code
Power display
calibration
P02.28
coefficient of motor
Parameter display
P02.29
of motor 1
System inertia of
P02.30
motor 1
P02.31–
Reserved
P02.32
coefficient.
A smaller value of "K" indicates a bigger value
of "M".
When M=116%, protection is performed after
motor overload lasts for 1 hour; when M=150%,
protection is performed after motor overload
lasts for 12 minutes; when M=200%, protection
is performed after motor overload lasts for 1
minute; and when M≥400%, protection is
performed immediately.
60
12
Setting range: 20.0%–120.0%
The function code can be used to adjust the
power display value of motor 1. However, it
does not affect the control performance of the
VFD.
1
Setting range: 0.00–3.00
0: Display by motor type. In this mode, only
parameters related to the present motor type
are displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0.000–30.000kg· m
-
Description
Time (min)
5
1
150% 180%
116%
2
-138-
Function parameter list
Default Modify
Motor overload
multiple
200%
1.00
0
0.000
2
kg· m
-
-