Goodrive350 IP55 High-ingress Protection Series VFD
Function
Name
code
P08.42
Reserved
P08.43
Reserved
UP/DOWN terminal
P08.44
control setting
Frequency
increment integral
P08.45
rate of the UP
terminal
Frequency integral
P08.46
rate of the DOWN
terminal
Action selection at
P08.47
power-off during
frequency setting
Description
Thousands
place:
compensation
0: No
1: Yes
-
-
0x000–0x221
Ones place: Frequency setting selection
0: The setting made through UP/DOWN is valid.
1: The setting made through UP/DOWN is
invalid.
Tens place: Frequency control selection
0: Valid only when
P00.06
1: Valid for all frequency setting methods
2: Invalid for multi-step speed running when
multi-step speed running has the priority
Hundreds place: Action selection for stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
0.01–50.00Hz/s
0.01–50.00Hz/s
0x000–0x111
Ones place: Action selection at power-off during
frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Tens place: Action selection at power-off during
frequency setting through Modbus/Modbus
TCP communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
-178-
Function parameter list
Output
voltage
= 0 or
P00.07
= 0
Default Modify
-
-
-
-
○
0x000
○
0.50Hz/s
○
0.50Hz/s
○
0x000