INVT Goodrive350 Series Operation Manual page 217

Ip55 high-ingress protection vfd
Hide thumbs Also See for Goodrive350 Series:

Advertisement

Goodrive350 IP55 High-ingress Protection Series VFD
Function
Name
code
Overload protection
P12.26
selection of motor 2
Overload protection
P12.27
coefficient of motor
Power display
calibration
P12.28
coefficient of motor
Parameter display
P12.29
of motor 2
System inertia of
P12.30
motor 2
P12.31–
Reserved
P12.32
0: No protection
1: Common motor (with low-speed
compensation)
2: Frequency-variable motor (without low-speed
compensation)
Motor overload multiples M=Iout/(In*K)
In is rated motor current, lout is VFD output
current,
coefficient.
A smaller value of "K" indicates a bigger value
of "M".
When M=116%, protection is performed after
motor overload lasts for 1 hour; when M=150%,
protection is performed after motor overload
lasts for 12 minutes; when M=200%, protection
is performed after motor overload lasts for 1
minute; and when M≥400%, protection is
performed immediately.
2
60
12
Setting range: 20.0%–120.0%
0.00–3.00
2
0: Display by motor type. In this mode, only
parameters related to the present motor type
are displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0–30.000kg· m
-
Description
K
is
motor
overload
Time (min)
5
1
150% 180%
116%
2
-199-
Function parameter list
Default Modify
protection
100.0%
Motor overload
multiple
200%
2
1.00
0
0.000
2
kg· m
-
-