Goodrive350 IP55 High-ingress Protection Series VFD
Function
code
P05.12
S1 switch-on delay
P05.13
S1 switch-off delay
P05.14
S2 switch-on delay
P05.15
S2 switch-off delay
P05.16
S3 switch-on delay
P05.17
S3 switch-off delay
P05.18
S4 switch-on delay
P05.19
S4 switch-off delay
P05.20
HDIA switch-on delay
P05.21
HDIA switch-off delay
P05.22
HDIB switch-on delay
P05.23
HDIB switch-off delay
Input terminal status at
P07.39
P17.12
Digital input terminal state
5.5.12 Digital output
The VFD carries two groups of relay output terminals, one open collector Y output terminal and
one high-speed pulse output (HDO) terminal. All the digital output terminal functions can be
used for programming through function code setting. The HDO terminals select high-speed
pulse output or digital output through function code setting.
0
1
2
0
3
1
4
5
P06.00
HDO
.
input type
.
.
.
29
30
The following table lists the function code options. A same output terminal function can be
repeatedly selected.
Name
present fault
Digital output selection
Digital switch-on delay
P06.06
Y
Switch-on
P06.01
delay
(Default value: 0)
HDO
P06.08
Switch-on
P06.02
delay
(Default value: 0)
ROI
P06.10
Switch-on
P06.03
delay
(Default value: 1)
RO2
P06.12
Switch-on
P06.04
delay
(Default value: 5)
Description
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0x0000–0xFFFF
Displays the present digital input terminal
state of the VFD.
0x00–0x3F
Corresponds to HDIB, HDIA, S4, S3, S2 and
S1 respectively.
P06.05 output polarity
selection
0
1
-1
0
1
-1
0
delay
1
-1
0
1
-1
-91-
Basic operation guidelines
Digital switch-off delay
Run
P06.07
Switch-off
delay
Fault
Fault
P06.09
Switch-off
delay
P06.11
delay
Switch-off
P06.05, P17.13, P07.40 display
delay
Y
BIT0
ROI
BIT2
P06.13
0: Open collector high-
Switch-off
P06.00
speed pulse output
delay
1: Open collector output
Default
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0x0000
0x00
P17.13
Digital output
terminal state
P07.40
Digital output
terminal state
of current fault
HDO
BIT1
RO2