5.5.2 Common commissioning procedure
The common commissioning procedure is as follows (taking motor 1 as an example).
Set vector control parameters
Note: If a fault occurred, find out the fault cause and remove the fault according to chapter 7
Troubleshooting.
Power up after confirming the
Asynchronous
motor
Set the motor parameters of
P02.01–P02.05 as per the motor
nameplate
If the motor rotates in wrong
direction, power off and exchange
the motor wires of any two phases,
Set autotuning mode (P00.15)
Complete parameter rotary
autotuning (P00.15=1)
Start autotuning after pressing
Set running command channel
SVC 0 (P00.00=0)
SVC 1 (P00.00=1)
Set vector control parameters
in P03 group
in P03 group
Run after a running command
Stop after a stop command is
Start
wiring is correct
Restore to default values
Synchronous
motor
Motor selection
(P02.00 or P12.00)
Set the motor parameters of
P02.15–P02.19 as per the motor
nameplate
Press QUICK/JOG to start
pilot run
and power on again
Complete parameter static
autotuning (P00.15=2)
RUN key, and stop after
autotuning is done
(P00.01, P00.02)
Set running frequency
Set speed control mode
(P00.00)
Space voltage vector control
mode (P00.00=2)
Set V/F parameters in P04
group
Set start/stop control
parameters in P01 group
is given
given
End
-41-
Basic operation guidelines
...
Partial parameter static
autotuning (P00.15=3)
FVC
(P00.00=3)
Set control parameters in P03
and P20 groups