Goodrive350 IP55 High-ingress Protection Series VFD
Note: This type of V/F curve separation can be applied in various variable-frequency power
sources. However, exercise caution when setting parameters as improper settings may cause
equipment damage.
Function
code
P00.00
Speed control mode
P00.03
Max. output frequency
Upper limit of running
P00.04
Lower limit of running
P00.05
P00.11
ACC time 1
P00.12
DEC time 1
P02.00
Type of motor 1
P02.02
Rated frequency of AM 1 0.01Hz–P00.03 (Max. output frequency)
P02.04
Rated voltage of AM 1
V/F curve setting of motor
P04.00
P04.01
Torque boost of motor 1 0.0%: (automatic); 0.1%–10.0%
Torque boost cut-off of
P04.02
V/F frequency point 1 of
P04.03
V/F voltage point 1 of
P04.04
Name
0: SVC mode 0
1: SVC mode 1
2: Space voltage vector control mode
3: Feedback vector control (FVC) mode
Note: Before using a vector control mode (0, 1,
or 3), enable the VFD to perform motor
parameter autotuning first.
P00.04–599.00Hz
P00.05–P00.03
frequency
0.00Hz–P00.04
frequency
0.0–3600.0s
0.0–3600.0s
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0–1200V
0: Straight-line V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
1
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F curve (V/F separation)
0.0%–50.0% (of the rated frequency of motor 1)
motor 1
0.00Hz–P04.05
motor 1
0.0%–110.0%
motor 1
Description
-53-
Basic operation guidelines
Default
2
50.00Hz
50.00Hz
0.00Hz
Model
depended
Model
depended
0
50.00Hz
Model
depended
0
0.0%
20.0%
0.00Hz
0.0%