Goodrive350 IP55 High-ingress Protection Series VFD
Function
Name
code
Proportional
coefficient of
P11.23
current regulator
during overvoltage
stall
Integral coefficient
of current regulator
P11.24
during overvoltage
stall
Enabling VFD
P11.25
overload integral
P11.26
Reserved
VF oscillation
P11.27
control method
SPO switch-on
P11.28
detection delay
time
SPO unbalance
P11.29
factor
P11.30
Reserved
Description
This parameter is used to set the proportional
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0–1000
This parameter is used to set the integral
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0–2000
0: Disable
1: Enable
When this parameter is set to 0, the overload
timing value is reset to zero after the VFD is
stopped. In this case, the determination of VFD
overload takes more time, and therefore the
effective protection over the VFD is weakened.
When this parameter is set to 1, the overload
timing value is not reset, and the overload
timing value is accumulative. In this case, the
determination of VFD overload takes less time,
and therefore the protection over the VFD can
be performed more quickly.
-
0x00–0x11
Ones place:
0: Method 1
1: Method 2
Tens place:
0: Reserved
1: Reserved
0.0–60.0s
Note: The SPO detection is started only after
the VFD runs for the delay time P11.28 to avoid
false alarms caused by the unstable frequency.
0–10
-
-194-
Function parameter list
Default Modify
○
60
○
250
◎
0
-
-
◎
0x00
○
5.0
○
6
-
-