Diagnostics and Error Handling
4.3 PU4 Test Command
4.3
PU4 Test Command
The Dialog Commands
4.3.1
NOTE
i
i
The SWT 3000 > Commands dialog is only online available (when connected to SWT 3000).
In the PowerSys dialog SWT 3000 > Commands, it is possible to select lines, enable LID/FOM Loops, or to
enable the AMP measuring.
[sc_swt3000_commands, 1, --_--]
Figure 4-10
The SWT 3000 > Commands dialog is divided into the following areas:
•
Line selection automatic (only if 2 transmission links are activated)
Automatic selection of the (primary) transmission line. If there is a fault, switchover to the alternative
(secondary) line.
•
Line selection primary (only if 2 transmission links are activated)
The SWT 3000 receiver is fixed to the primary transmission line. This setting causes the general alarm.
•
Line selection secondary (only if 2 transmission links are activated)
The SWT 3000 receiver is fixed to the secondary transmission line. If there is a line interrupt, switchover is
not possible. This setting causes the general alarm.
188
PowerSys Dialog SWT 3000 > Commands
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020