[scen100h-260313-01.tif, 1, en_US]
Figure 4-16
NOTE
i
i
With a factory pre-configuration of EN100 in SWT 3000 devices the following generic IP addresses are
programmed to the module: 192.168.100.11 and 192.168.100.12.
You can check the actual IP address of the EN100 module in PowerSys menu SWT 3000 > Information >
EN100 Info (refer to EN100 Information in PowerSys).
The EN100 module homepage always shows at its end the version and creation date of the software version
loaded on the module. With the links on the left area of the EN100 homepage you can browse to following
subpages, which contain information for commissioning, operational information and internal error messages.
Table 4-13
Page
Statistics-page
System log-page
Connection log-page
Startup-page
Error log-page
Refer to SIPROTEC 4 EN100-Module - Manual IEC 61850 for description of the pages.
You may find a copy of the manual on the PowerSys-DVD in folder /IEC61850/Manual.
Check the SIPROTEC webpage for the latest manual version:
Internet:
www.siprotec.com
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Homepage of the EN100 modules
Linked pages of the EN100 module homepage
Description
shows relevant information of Ethernet
shows information of system behavior, being produced from operation time
contains information about Client-Server-Connection and DIGSI-Accesses
contains information about run-up behavior and configuration settings
respecting network- and GOOSE-Parameters
contains internal error messages
Diagnostics and Error Handling
4.7 Diagnosis of Ethernet EN100 Module