Functional Description
2.11 IEC 61850
[DwReportGoo, 1, en_US]
Figure 2-21
Redundancy
The EN100 communication module supports several operating modes Line, RSTP, PRP, HSR and OSM. This
allows integrating a SWT 3000 device into nearly all network structures. Redundancy is important for the relia-
bility of an entire communications system. If the link of the active channel is interrupted, switchover to the
other interface is automatic. If all channels are interrupted, SWT 3000 device will report a non-urgent alarm
(EN100_QUAL: EN100 communication quality is not OK).
MergeTool provides following setting file which enables different redundancy settings.
Setting file
swt3000_en100_settings_LINE_SnmpOFF_HttpOFF.ifd
swt3000_en100_settings_LINE_SnmpON_HttpON.ifd
swt3000_en100_settings_RSTP_SnmpON_HttpON.ifd
swt3000_en100_settings_PRP_SnmpON_HttpON.ifd
swt3000_en100_settings_HSR_SnmpON_HttpON.ifd
74
Example for a Report and GOOSE Communication
Operating
Redun-
mode
dancy type
Line
---
Line
---
Switch
RSTP
Switch
PRP
Switch
HSR
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
SNMP
HTTP service
service
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON