Siemens SWT 3000 Equipment Manual page 77

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

LN: RXC_GGIO - Receive command
Table 2-21
GGIO class
Data object
Commo
name
n data
class
LNName
Data objects
Common Logical Node Information
Measured values
Status Information
Controls
SPCSO1
SPC
SPCSO2
SPC
SPCSO3
SPC
SPCSO4
SPC
SPCSO5
SPC
SPCSO6
SPC
SPCSO7
SPC
SPCSO8
SPC
SPCSO9
SPC
SPCSO10
SPC
SPCSO11
SPC
SPCSO12
SPC
SPCSO13
SPC
SPCSO14
SPC
SPCSO15
SPC
SPCSO16
SPC
Table 2-22
ITPC class
Data object
Name
LNName
Data objects
EEHealth
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
LN: RXC_GGIO - Receive command
Explanation
Name composed of the class name, the LN-Prefix and LN-Instance- ID
according to IEC 61850-7-2
Single point controllable status output.
Command input 1, which acts as an input for the local SWT processing.
Attribute ctlVal is assigned to the SWT command input. The input status is
not trans-ferred transparent to the remote side! It depends on the actual
SWT-Mode, how a change of ctlVal influences the command outputs on the
remote SWT.
Command output 2
Command output 3
Command output 4
Command output 5
Command output 6
Command output 7
Command output 8
Command output 9
Command output 10
Command output 11
Command output 12
Command output 13
Command output 14
Command output 15
Command output 16
LN: ITPC - Communication Interface
Common data
Explanation
class
Name composed of the class name, the LN-Prefix and LN-
Instance- ID according to IEC 61850-7-2
ENS
External equipment health.
It reflects the alarm status of the SWT device. Possible values:
1: Ok (Green) no alarms active
2: Warning (Yellow) only none urgent alarms active
3: Alarm (Red) at least one urgent alarm is active
Functional Description
2.11 IEC 61850
T
M/
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
T
M/O
O