Vacm Management - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

[sccloneu-140912-01.tif, 1, en_US]
Figure 6-8
5 - The new user "testuser" is cloned from templateMD5, whose authentication and privacy passwords are
same as templateMD5.
[scusmuse-140912-01.tif, 1, en_US]
Figure 6-9
6 - Change the authentication password and the privacy password. For example:
Auth password: "testuser_auth"
Priv password: "testuser_priv"
NOTE
i
i
It is recommended to have at least 8 characters for the password.
7 - Assign access right for the new cloned user (see Example: Assign Access Right)
NOTE
i
i
This step is not needed for the SWT 3000 standalone device. The new cloned user has full access right to
complete MIB modules and it cannot be changed by the user via VACM.
8 - Check if new working user can connect to SNMP agent. Remove initial and template users as soon as
all desired working users have been created.
9 - Store all the configurations to flash and restart system through SNMP by setting following MIB object:
SIEMENS-SWT3000R35-MIB::swtIpActivationReq.0 = storeToFlashAndRestart(1)
NOTE
i
i
For all detail operation steps, check the user manual of your MIB Browser.
6.2.3.4

VACM Management

Definition
VACM controls the access right of the user to the MIB object, which is accomplished through SNMP by setting
MIB module SNMP-VIEW-BASED-ACM-MIB.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Clone New User
USM User Table List
SNMP and Remote Access
6.2 SNMP
283

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents