Siemens SWT 3000 Equipment Manual page 152

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

Installation and Commissioning
3.5 Device Configuration
NOTE
i
i
The EN100-IEC 61850 feature is disabled if EN100-TPoP is configured. Only binary command input and
output can connect to SWT 3000.
Ethernet line interface parameters are configured in PowerSys under SWT 3000 > Configuration > Ethernet
line interface > Configuration (see next figure).
[ScEthConf-27032014-01, 1, --_--]
Figure 3-45
Table 3-51
Parameter
IP address
Gateway
Subnet mask
Peer IP address
Port number
HMAC algorithm
Password
Retype password
Min. command repeat
interval [read-only]
Max. command repeat
interval [read-only]
Packet loss rate threshold Packet loss rate alarm threshold. If it is set to zero, the packet loss rate alarm is
152
Ethernet Line Configuration
Comments
User-defined IP address
For a pair of SWT 3000 devices A+B:
Device A: 192.168.100.11 (Subnet: 255.255.255.0)
Device B: 192.168.100.12 (Subnet: 255.255.255.0)
User-defined default gateway
User-defined subnet mask
User-defined IP address of remote SWT 3000 device
User-defined UDP port number for TPoP service
Authentication algorithm used in Ethernet communication. Default value is
HMAC-SHA256.
Off : HMAC are not enabled
HMAC-SHA256: Message authentication using hash function SHA256 is enabled.
Secure password used in HMAC algorithm. It must not be empty if HMAC is
enabled and must be the same for remote SWT 3000 devices.
Retyped password must be the same as the original password.
Minimum transmission time interval for repeat command packet. Default value is
2 ms.
Maximum transmission time interval for repeat command packet. Default value is
1000 ms.
switched off. Default value is 5%.
Possible value: 0 to 100% in steps of 1%.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020