Functional Description
2.7 Protection Modes
Timeline
t4
t5
t6
t7
It is possible to enable fast transmission of permissive command with additional setting in PowerSys as below:
•
"BI1+2 interrupt single command BI1 or BI2 without delay" is enabled. Permissive command 1 or 2 trans-
mission can switch to input combination 1+2 without waiting for minimal transmission duration time-
out.
•
Transmission duration for permissive command is set to 15 ms. Permissive command is transmitted for at
least 15 ms.
•
Pulse suppression for permissive command is set to 0 ms. Permissive command input is accepted without
additional delay by suppression timer.
For detailed settings, refer
[DwFastComm020215, 1, en_US]
Figure 2-10
Table 2-10
Timeline
t1
t2
t3
t4
t5
t6
t7
56
Description
BI1 active, start transmission of command 1.
BI2 active after time interval 2 ms, continue transmission of command 1.
Transmission duration time-out, switch to transmit command 2, BO1 inactive after
command transmission delay.
Transmission duration time-out, BO2 inactive after command transmission delay,
switch to transmit guard command.
toTable 3-42
and
Fast Transmission of Permissive Command 1+2
Fast Command Transmission Timeline Description
Description
BI1 active, start transmission of command 1.
BI2 active within time interval 2 ms, switch to transmit command combination of 1+2,
BO1+2 active after command transmission delay.
Transmission duration time-out, BO1+2 inactive after command transmission delay.
BI1 active, start transmission of command 1, BO1 active after command transmission
delay.
BI2 active after time interval 2 ms, switch to transmit command combination of 1+2,
BO2 active after command transmission delay.
Transmission duration time-out, switch to transmit command 2, BO1 inactive after
command transmission delay.
BI2 inactive, switch to transmit guard command, BO2 inactive after command transmis-
sion delay.
Table
3-43.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020